Tuesday, November 20, 2012

Retrofitting of Existing Fire Alarm Systems




Anthony J. Shalna, CET
John M. Stofa, CET  

Executive Summary - The disastrous Station Night Club Fire in Warwick Rhode Island back in February of 2003 cost many lives and resulted in the updating and tightening of fire alarm codes not only in Rhode Island, but in many other cities, states and localities as well. To date, the Station Night Club Fire has resulted in $176 million in damages, as well as jail terms for the culpable person(s) found to be negligent.

Coupled with the tougher fire codes is the fact that the down economy has slowed new construction starts drastically since 2007.  However, fire alarm system retrofits, that is, the replacing of obsolescent head-end systems with new head-end systems is becoming more popular, due to the advent of microprocessor-based systems and the lower cost of a retrofit as compared to a full system installation. Retrofits when planned carefully with a proper migration plan and installed according to all standards and codes make good business sense, but an alarming number of retrofits are falling short of meeting the fire alarm codes, creating a major liability and safety issue for all parties concerned.

Another affect of the current economic condition is the fact that fewer municipalities have funds available for the training of the Authority Having Jurisdiction (AHJ), Fire Prevention Departments, Fire Inspectors and Fire Marshalls who are responsible for signing-off on fire alarm installation projects and certifying that the installation complies with all applicable codes.

The purpose of this report is to point out some very obvious and not so obvious concerns in regard to fire alarm system retrofitting. It is to be considered as a “guide only”, and by no means is it to be considered a comprehensive set of instructions on how to perform a fire alarm system retrofit.










Equipment Cabinets – The idea that an existing fire alarm system cabinet can be retrofitted with new electronics equipment is one that can potentially save a significant amount of money for the end-user.  The reuse of the cabinet will more than likely save days of labor hours because the electrician installing the new system does not need to uncouple the existing conduits, remove the existing wiring, reconnect the conduits and then reconnect the wiring into the new cabinet.  However, if you intend to re-use existing fire alarm cabinets, these cabinets must be listed or approved by a Nationally Recognized Testing Laboratory (NRTL) for the specific control equipment being installed. The fact that the existing cabinet has an NRTL sticker affixed to it means nothing if the report or installation manual doesn’t specify that particular cabinet as being acceptable for use with the new electronic sub-assemblies involved.

The NRTL report is very specific about the cabinets and subassemblies required for a fire alarm control panel. This information is echoed in the system installation manual, which is also part of the NRTL report.

Modification of an existing cabinet by cutting, drilling or any other modifications will void any NRTL listing and automatically become a code violation unless the modification is approved or directed by the AHJ. An example of this would be addition of a component specified by local ordinance or regulation such as a special key cylinder for smoke control activation. Likewise, placing new subassemblies in an existing unapproved cabinet is also a violation. Some reasons are:

1.)  A restriction or lack of air flow circulation could cause excess temperatures and possible component failure or performance issues.
2.)  Routing of power limited and non-power limited wiring must be as specified in the new fire panel control panel manual.
3.)  Existing wiring routing may contradict the power limited or non-power limited wiring required for the new system.
4.)  Existing backboxes may not take into account RF and EMF issues corrected by the modern backbox thus leading to performance issues.

The new control panel will have a label affixed to the inside of the door that contains pertinent listing and wiring information, including the approved power limited and non-power limited wiring layout diagram(s). Modification of an existing door would mutilate the door label which is a violation.  While a re-used door would contain an obsolete label; which should be a red flag to the competent and alert AHJ.

Excess high and low temperatures must also be considered.  If the panel is relocated as part of the retrofit, recommended ambient temperatures may be exceeded. For example, locating a panel in a protected, but unheated outdoor enclosure may subject the panel to ambient temperatures outside the listed limits again causing unpredictable performance issues.  Likewise, installing a panel in an area where the ambient temperatures are allowed to exceed the recommended operating temperature listed by the manufacturer could also result in performance issues.


Wiring – In the past, fire alarm codes were more relaxed in regard to the type of wire used in fire alarm systems. If the original installation pre-dates the advent of power-limited wiring requirements for fire alarms, the entire system will more than likely need to be re-wired.  The comingling of power-limited and non-power limited wiring is against the National Electric Code and will cause major performance issues if allow to happen.  This is one of the most frequently violated codes when dealing with sub-par installations performed by less than professional installers.

Furthermore, new addressable fire alarm systems transfer data packets from the field devices to the control panel and vise versa.  Older wiring used with conventional type systems was not designed for the transmission of data but rather was used to determine a “make/break” condition and to measure the value of the End of Line Resistor.  The expectation of being able to re-use this older wiring for a high performance microprocessor based fire alarm system is an unrealistic expectation of the wiring’s capabilities.

Finally, issues that the client is experiencing with their existing fire alarm system such as ground faults, shorts, wet/weather issues and raceway protection issues will not be corrected by simply replacing the fire alarm control panel.  Misleading the client into thinking that those issues will magically go away is considered negligence.  The problems with the field wiring must be found and fixed or they will carry over to the new system and leave the client dissatisfied and frustrated.






Compatibility Issues – This area is often misunderstood and can present a serious problem. Establishment of compatibility is required for 2-wire smoke sensors/detectors, electronic initiating devices, addressable monitor and control modules, notification appliances, and releasing solenoids. 4-wire smoke detectors are in the process of being included since some power supplies have been found to be outside the operating limits of these detectors.

Each panel manufacturer issues an NRTL listed/approved compatibility document that lists the various devices that are compatible with their corresponding fire alarm control panel. The panel Installation & Operating Manual may also contain this information. A smoke sensor manufacturer may also publish a compatibility document that is NRTL listed/approved.
If the device in question is not listed in any of these documents, then it is NOT COMPATIBLE and MUST NOT REMAIN IN SERVICE.  If the installer intends to re-use existing 2-wire smoke detectors, the existing detectors must be included in the compatibility documentation.

Compatibility for 2-wire smoke detectors is not simply a matter of comparing current ratings of the detectors and initiating circuits. Unlike a contact closure device that places a short circuit across the initiating device circuit, the 2-wire detector, when it goes into alarm, presents an impedance across the circuit that is low enough to place the circuit into alarm, but not too low to prevent enough current to hold the detector in alarm, and keep the indicating LED lit. This depends on the area of intersection of response curves of both the detector and initiating circuit. All these calculations are also involved in determining the capacity of the initiating circuit as to the quantity of detectors that may be installed on it. The compatibility documents/manuals also state this information.

A major pitfall of retrofitting is mixing of different quantities of different models or brands of 2-wire detectors on the same circuit. Unless this combination is listed in an NRTL document, any mixing of models/brands would violate the listing. No one can predict what combination of models/brands/quantities would work properly. Only a qualified testing laboratory could verify and certify its operation.

Another area affecting compatibility is smoke level compensation. New generation microprocessor-based detectors have the ability to adjust their own sensitivity to compensate for dirt/dust build-up in the detector, smoke build-up, or gradual changes in the ambient environment. Re-installation of compensated detectors could result in unwanted alarms and subsequent frustration for the building owner.  It is always a “best practice” to clean any existing smoke detector that is going to remain and subsequently be re-used with the new fire alarm control panel. 

Often a smoke detector manufacturer will purchase a competitor’s fire alarm control panel on the open market in order to test their detectors with this panel, have the results verified by an NRTL, and publish the information in their own document. If you choose to use devices listed in a document published by a smoke sensor manufacturer rather than by the panel manufacturer, be aware of a possible problem. The panel manufacturer will assume no responsibility if the devices are not listed in his own document, since the detectors, “by others” were not furnished by him, or haven’t been tested by him. The reasoning here is the panel manufacturer has nothing to gain and everything to lose by approving a product not sold by him. Also, since the panels tested were purchased on the open market by the detector manufacturer, there is a possibility that the individual tested panel may have been damaged, improperly stored, or is from a production run that exhibited quality assurance problems, etc. This could eventually result in litigation that would only be settled in the courts.

And in conclusion ,with the exception of household, one and two family dwelling smoke detectors, requirements have not yet been established regarding the useful life (expiration date) of smoke sensors.  However the National Fire Alarm and Signaling Code, NFPA 72, calls for reacceptance testing whenever fire alarm control equipment is replaced or reprogrammed.  Electronic components age with time, filter screens may become clogged or partially clogged, materials become brittle with age, etc. Plan on and budget for the replacing of any smoke sensors or devices that fail the reacceptance test. 


Manual Pull Stations (Boxes) – The Americans with Disabilities Act (ADA) specifies requirements for the manufacturing of pull stations and these requirements are now being enforced. The ADA requires a maximum pull force of five (5lbs.) pounds to operate a manual pull station. Many older manual pull stations do not meet this requirement.

Also, ADA specifies the mounting height of the manual pull stations, which may require relocation of existing non-compliant pull stations. Formerly, fire officials mandated placing the pull stations high enough to discourage children from activating a false alarm. Now due to ADA requirements, they must be mounted low enough for a person in a wheelchair to reach the pull station’s actuating lever.

 

Batteries - In most cases the fire alarm control panel installation manual will be specific regarding the model of batteries to be used. This manual is part of the NRTL report and therefore spells out the Listing.

Batteries designed for fire alarm signaling use will yield a steady current for a prolonged period of time. Appliance or automotive type batteries are designed to produce a high output for a short period of time and are not adequate or appropriate for fire alarm system use.

In addition, the instructions may specify replacement of the batteries after a certain period. An improperly selected battery might not last long enough to reach the replacement interval, and may fail during a power outage. Also, were the original batteries installed in an area where it could be exposed to excess temperatures? Were they properly maintained? Excessive heat or improper maintenance will shorten battery life considerably.


Notification Appliances – These devices are straightforward and far less complicated than sensor installations, but the newest panels depending on line voltage extremes, may present greater operating voltages which are outside the range of the existing notification appliances. 

Since most NAC circuits are wired in a conventional fashion, the use of End of Line Resistors (EOLR) is still mandated on some circuits in order to maintain supervision of the circuit.  As the name states, the resistor is to be placed at the end of the line. Any resistor mounted within the panel on any NAC circuit needs to be scrutinized.  This EOLR mounted in the panel may elude even the best trained AHJ at times. 

The ADA requires the synchronization of flashes for strobe lights under most conditions; always wherever more than one strobe is observable at the same time. This is due to the fact that certain rapid uncoordinated flash rates have been known to cause epileptic seizures in persons prone to this affliction. Older installations may have to be re-engineered and new equipment deployed with this requirement in mind.

Current ADA requirements may also affect mounting heights of appliances, so existing appliances may need to be relocated if they are outside the acceptable range. 

Until recently, some jurisdictions have required that after an “alarm” and before the “system reset”, that the audible signals be silenced, but the strobes must continue to flash. It’s now being presented to them that to a hearing impaired person, a flashing strobe is an evacuation signal. Therefore, this regulation is in conflict with the codes that call for both audible and visual signals to be extinguished when the “signal silence” feature is activated following an evacuation.


Local Energy Master Boxes - Master Boxes are still in use in some parts of the country, notably New England and a number of military bases. All Master Boxes manufactured in the last 20 years or so are NRTL listed by the manufacturer. A number of repaired, refurbished or rehabilitated master boxes have been appearing in both new and retrofit installations. Occasionally a few of these master boxes still retain the original NRTL label. Re-use of this label on a “rebuilt” box could be interpreted as fraud, since repairing or rehabilitating a master box by someone other than the manufacturer voids any NRTL listing. Since the code states that all equipment must be listed for the purpose intended, installation of an unlisted master box would be a glaring violation of the code and open wide the door for liability in the event of a tragedy.

Furthermore, the installation of new electronic solid state and/or radio master box systems within older existing legacy master box shells has become a plague sweeping the industry in the last decade as cities and town no longer have the funding to maintain their 100 mil cable plants.  This practice should also be considered fraud since the electronic and radio master box equipment typically is not listed by a NRTL to be installed within the existing master box enclosure.  This fact is not made known to the customer when the new electronic system is purchased and installed and therefore the customer is unaware that they have been sold a system that does not meet any NRTL requirements.  Again, subjecting everyone involved to legal implications should the non-compliant electronic or radio master box system fail to operate when needed.




Documentation – Older installations may have existed before the codes required the submittal of “As-Built” drawings. A retrofit installation requires creation of these drawings and proper storage of them. In addition, battery standby calculations are also now required when submitting fire alarm layouts to the AHJ for permitting.

Battery calculations previously used a safety multiplication factor at the end, recommended by the battery manufacturer, to cover minor differences in various batteries stored under different conditions, etc. That factor is now or is in the process of being doubled, which might have a significant effect on the size of batteries required, so the codes should be checked and referenced in this regard.

Conclusion



In summary, the retrofitting of an older fire alarm system with a new modern fire alarm control panel is good business and can save the client or end-user thousands of dollars as compared to a new complete fire alarm installation. However, it must be understood that a properly installed retrofit system shall comply with all of the listing requirements, codes and precautions that accompany a new installation.  Deviation and corner cutting to navigate around these rules will result in unnecessary damage to property and possible loss of life which is unacceptable to true Life Safety Experts and Industry Professionals.

Sunday, November 18, 2012

No Budget for Training?  Call on the Factory!

By John M. Stofa  copyright 2012


It’s no secret that the economic downturn has caused significant changes to the fire service and forced all departments to do more with less.  One of the first casualties due to funding shortfalls has always been the Training & Education budget.  So how do you continue to provide your team with the most meaningful and up-to-date educational information available, but do so on a shoe string budget?  Simple, ask your product and apparatus manufactures to help out.




First Shift Engine, Truck and Rescue Company being trained on fire alarm and sprinkler systems at a state of the art training facility in town.





Manufactures and Product Sales Representatives are always looking for opportunities to provide training not only on their products, but also on trends in their industry and new and emerging technologies.  This training can easily be changed and edited to remove the “sales pitch” and deliver education and informational sessions that your team will appreciate.  The best part is most manufactures reps are more than willing to do the training, they often times will issue certificates for the training session, and they do not charge for their time!  This is a win/win for all involved and should be a resource that is tapped into as often as necessary. 

Some of the available training topics are listed below.  This is by no means an all inclusive list and you should ask all manufactures what they can offer.  Topics such as:

-         Fire Alarm Operations
-         Elevator Operations & Rescue Tactics
-         Mass Notification Systems
-         ADA Requirements & Life Safety
-         Voice Fire Alarm System Intelligence Testing
-         Sprinkler System Corrosion Prevention
-         In-Building Fire Pump Operations
-         Special Hazard Systems
-         Video Smoke Detection
-         Air Aspirating Detection Systems
-         Carbon Monoxide Detection
-         Industrial Gas Detection
-         Turnout Gear & Fall Protection Innovations
-         Fire Apparatus Innovations
-         Safe Driver Training
-         Bloodborne Pathogens & Communicable Disease Training



Another benefit of receiving training from your product manufacture is the fact that they are up-to-date on the latest codes and regulations as well as being aware of trends coming down the pike and future legislation.  This will give your staff the ability to learn about technologies and tactics that are emerging before they need to deal with th1em in the field.  This “getting ahead of the curve” if you will, could prove vital and valuable during an emergency operation and help give your team the edge that they need.

As a manufacture’s rep myself in the fire alarm and detection industry, it is always exciting and refreshing to be asked to speak to a fire department about the products and technologies available today and what is coming out tomorrow. It also helps to make the connection between the drawing board for products and the first responder who ultimately interfaces with the product.  It gets everyone onto the same collective page which is priceless especially when everyone’s mission is to save and protect people and property. 
Pre WWII Detector Technology in a
Modern World? – Time to force a change…
By John M. Stofa Copyright 2012

One of the best kept secrets from the fire service is the fact that within the last 15 years, commercial smoke detection in the fire alarm industry has advanced significantly. It has advanced to the point where the common “system connected” smoke detector is now able to distinguish the smoke from a real fire event against other particles or conditions which could cause a false alarm. Yet the majority of system connected smoke detectors manufactured, sold and installed today simply do not employ such technology. As a matter of fact, we continue to rely on the tried and true single-criteria smoke sensor which was first developed in the 1930’s. And in most cases the ionization or photo-electric smoke sensor is the detector of choice for today’s installation. But is this good enough? Quite simply the answer is no. We should expect and demand more advanced performance from a modern smoke detector, and the technology and products already exist.

Studies have been performed over and over again; and they have proven positively that “false alarms” or what we in the alarm industry preferred to call “nuisance alarms” could be avoided if multi-criteria smoke detectors were installed in conjunction with the routine cleaning, inspection and testing of the smoke detector. The term “false alarm” is just not a true representation of the alarm condition. The system and its detectors are reacting normally, but they may be alarming due to dust, power spikes, insects, steam, or physical conditions other than smoke. Therefore the alarm isn’t false; a false alarm would mean that the system just decided to go off for no apparent reason whatsoever and the genesis of the alarm could not be explained. Today’s modern fire alarm systems have advanced to the point that these false alarms no longer happen. There is always a reason why the system alarmed, and hopefully as first responders we are looking for that cause and not simply pushing the panel’s reset button and hoping that the system clears so that we can close out the call with a disposition of “false alarm, no apparent cause”.


Single-Criteria Smoke Detector
Photo Electric or Ionization Only


Multi-Criteria Smoke Detector
Photo Electric or Ionization
and/or
Heat Sensing
Infrared Sensing (IR)
Carbon Monoxide Sensing
Laser Smoke Sensing
So what is a multi-criteria smoke detector? Simply put, it is a smoke sensor that uses two or more elements or criteria to sense and detect the presence of smoke and/or the by-products of combustion from a fire. Sensing elements such as photo-electric smoke detection, infrared (IR) light signatures, fixed heat or a rapid rise in temperature and/or the presence of carbon monoxide gas are measured and used together within a “smart” sensor to distinguish what is truly a smoke or fire condition from what is a non-life threatening or nuisance condition.

But rather than require and enforce the use of advanced technology to distinguish what is a real smoke condition from a nuisance alarm, we now see that some jurisdictions are changing their SOPs and stepping down there first response to automatic alarm activations. Or worst yet they are holding up or retarding the dispatch process in order to call the premises to verify if there is a smoke condition or other valid reason for the alarm signal. This sounds like a dangerous workaround to a simple problem. A workaround that could result in the loss of life due to the time lost, and most certainly allow a fire to grow in size, or help advance the spread of smoke.

So if better technology exists that could reduce the “nuisance alarm” problem, then why do we not see more of these “smart” detectors employed? The main problem is of course money. When outfitting a building with a new fire alarm system, the main concern typically is “how much will the fire alarm installation cost and what is the minimum that I need to do?”, and not “what is the best protection that I can reasonably buy?”. The backend aftermarket costs such as maintenance and “nuisance alarm response” are not usually considered or discussed because the end-user is very much removed from the design and installation process and doesn’t get involved until the commissioning process or until they have beneficial use of the system.

So how much more does the basic multi-criteria smoke detector cost? About $24 per smoke detector more than a single-criteria detector. This may sound like a big price difference, but think about that vs. the cost of being fined for multiple nuisance alarm responses or the safety of the first responders. Over the lifetime of both the building and the fire alarm system, this cost difference is negligible and if it saves the life of a firefighter possibly being needlessly killed while responding to a nuisance alarm, it is priceless…

So how do we get building owners who are not required to install multi-criteria smoke detectors today to actually use such technology? Local Fire Departments, Inspectors, Fire Marshalls and AHJs (Authority having Jurisdiction) must push to change and update all applicable local and state codes to require the use of multi-criteria smoke detectors, and outlaw the use of new single-criteria smoke detectors. Much like we pushed to eliminate the use of antiquated and dangerous single jacket hose lines, the time has come to shift the community to a better detector technology and enforce the change. Going forward it would be the best way to protect people and property, and hopefully prevent the senseless death of a first responder due to a nuisance alarm. The technology is available, let’s embrace it.